Control Specifications |
Control Method |
Soft-PWM control/high carrier frequency PWM control (V/F control, General-purpose magnetic flux vector control, Optimum excitation control can be selected) |
||
Output Frequency Range |
0.2 to 400Hz |
|||
Frequency Setting Resolution |
Analog Input |
0.06Hz/60Hz (terminal2, 4: 0 to 10V/10bit) 0.12Hz/60Hz (terminal2, 4: 0 to 5V/9bit) 0.06Hz/60Hz (terminal4: 0 to 20mA/10bit) |
||
Digital Input |
0.01Hz |
|||
Frequency |
Analog Input |
Within ±1% of the max. output frequency (25°C ±10°C) |
||
Digital Input |
Within 0.01% of the set output frequency |
|||
Voltage/Frequency Characteristics |
Base frequency can be set from 0 to 400Hz. Constant torque/variable torque pattern can be selected |
|||
Starting Torque |
150% or more (at 1Hz) when General-purpose magnetic flux vector control and slip compensation is set |
|||
Torque Boost |
Manual torque boost |
|||
Accel. /Decel. Time Setting |
0.01 to 3600s (acceleration and deceleration can be set individually), linear or S-pattern acceleration/deceleration mode can be selected. |
|||
Braking Torque |
Regeneration (*1) |
FR-D720-008 and 014, FR-D720S-008 and 014, FR-D710W-008 and 014 ... 150%, FR-D720-025 and 042, FR-D740-012 and 022, FR-D720S-025 and 042, FR-D710W-025 and 042 ... 100%, FR-D720-070, FR-D740-036, FR-D720S-070 ... 50%, FR-D720-100 or more, FR-D740-050 or more, FR-D720S-100 ... 20% |
||
DC Injection Brake |
Operation frequency (0 to 120Hz), operation time (0 to 10s), operation voltage (0 to 30%) variable |
|||
Stall Prevention Operation Level |
Operation current level can be set (0 to 200% adjustable), whether to use the function or not can be selected |
|||
Operation Specifications |
Frequency Setting Signal |
Analog Input |
Two points |
|
Digital Input |
Entered from operation panel and parameter unit. Frequency setting increments is selectable. |
|||
Start Signal |
Forward and reverse rotation or start signal automatic self-holding input (3-wire input) can be selected. |
|||
Input Signal |
Five points. You can select from among multi-speed selection, remote setting, second function selection, terminal 4 input selection, JOG operation selection, PID control valid terminal, external thermal input, PU-external operation switchover, V/F switchover, output stop, start self-holding selection, forward rotation, reverse rotation command, inverter reset, PU-NET operation switchover, external-NET operation switchover, command source switchover, inverter operation enable signal, and PU operation external interlock |
|||
Operational Functions |
Maximum/minimum frequency setting, frequency jump operation, external thermal relay input selection, automatic restart after instantaneous power failure operation, forward/reverse rotation prevention, remote setting, second function, multi-speed operation, regeneration avoidance, slip compensation, operation mode selection, offline auto tuning function, PID control, computer link operation (RS-485), Optimum excitation control, power failure stop, speed smoothing control, Modbus-RTU |
|||
Output Signal |
Output Signal Points |
Open Collector Output |
One point |
|
Relay Output |
One point |
|||
Operating Status |
You can select from among inverter operation, up-to-frequency, overload alarm, output frequency detection, regenerative brake prealarm, electronic thermal relay function prealarm, inverter operation ready, output current detection, zero current detection, PID lower limit, PID upper limit, PID forward/reverse rotation output, fan alarm (*3), heatsink overheat pre-alarm, deceleration at an instantaneous power failure, PID control activated, PID output interruption, during retry, life alarm, current average value monitor, remote output, alarm output, fault output, fault output 3, and maintenance timer alarm |
|||
For Meter Output Points |
Analog Output |
0 to 10VDC: one point |
||
For Meter |
You can select from among output frequency, output current (steady), output voltage, frequency setting, converter output voltage, regenerative brake duty, electronic thermal relay function load factor, output current peak value, converter output voltage peak value, reference voltage output, motor load factor, PID set point, PID measured value, output power, PID deviation, motor thermal load factor, inverter thermal load factor 0 to 10VDC |
|||
Indication |
Operation Panel Parameter Unit (FR-PU07) |
Operating Status |
You can select from among output frequency, output current (steady), output voltage, frequency setting, cumulative energization time, actual operation time, converter output voltage, regenerative brake duty, electronic thermal relay function load factor, output current peak value, converter output voltage peak value, motor load factor, PID set point, PID measured value, PID deviation, inverter I/O terminal monitor, output power, cumulative power, motor thermal load factor, inverter thermal load factor, PTC thermistor resistance. |
|
Fault Definition |
Fault definition is displayed when the fault occurs and the past 8 fault definitions (output voltage/current/frequency/cumulative energization time right before the fault occurs) are stored |
|||
Additional Display By The Parameter Unit (FR-PU07) Only |
Operating Status |
Not used |
||
Fault Definition |
Output voltage/current/frequency/cumulative energization time immediately before the fault occurs |
|||
Interactive Guidance |
Function (help) for operation guide |
|||
Protective Functions |
Overcurrent during acceleration, overcurrent during constant speed, overcurrent during deceleration, overvoltage during acceleration, overvoltage during constant speed, overvoltage during deceleration, inverter protection thermal operation, motor protection thermal operation, heatsink overheat, input phase loss (*5, *6), output side earth (ground) fault overcurrent at start (*5), output phase loss, external thermal relay operation (*5), PTC thermistor operation (*5), parameter error, PU disconnection, retry count excess (*5), CPU fault, brake transistor alarm, inrush resistance overheat, analog input error, stall prevention operation, output current detection value exceeded (*5), safety circuit fault |
|||
Warning Functions |
Fan alarm (*3), overcurrent stall prevention, overvoltage stall prevention, PU stop, parameter write error, regenerative brake prealarm (*5), electronic thermal relay function prealarm, maintenance output (*5), undervoltage, operation panel lock, password locked, inverter reset, safety stop |
|||
Environment |
Surrounding Air Temperature |
-10°C to +50°C (14°F to 122°F) (non-freezing) (*4) |
||
Ambient Humidity |
90%RH maximum (non-condensing) |
|||
Storage Temperature (*2) |
-20°C to +65°C (-4°F to 149°F) |
|||
Atmosphere |
Indoors (without corrosive gas, flammable gas, oil mist, dust and dirt, etc.) |
|||
Altitude/Vibration |
Maximum 1000m (3280.80 feet) above sea level, 5.9m/s2 or less at 10 to 55Hz (directions of X, Y, Z axes) |